Products

Halogen-Free Cables

SABIX® A 226 C FRNC C1

Halogen-Free Control Cables CE

SERIES #: 6226

Low smoke halogen-free (LSHF) shielded SABIX® control cable with black numbered conductors with improved fire performance and temperature range for railway applications acc. to NC C 32-070-C1 - 750V, +90°C

Download PDF
SABIX® A 226 FRNC C1- SAB Halogen Free Cables (SABIX)

Marking for SABIX® A 226 FRNC C1 62261207:
SAB BRÖCKSKES D-VIERSEN · SABIX® A 226 FRNC C1 12 x 0.75 mm² CE

CE
RoHS
PFAS-Free

Application

With proven quality, the SABIX® A 226 C FRNC C1 series provides consistent performance in industrial control systems. Low smoke halogen-free (LSHF) shielded SABIX® control cable with black numbered conductors with improved fire performance and temperature range for railway applications acc. to NC C 32-070-C1 - rated for 750 V, up to 90°C. It is built with a SABIX® jacket for durability and resistance in harsh conditions. With approvals such as CE, RoHS, it meets key international standards. This series also offers halogen-free to perform in demanding environments. It ensures lasting durability and supports smooth integration into control panels and automated systems.

Outstanding Features

» Low smoke halogen-free (LSHF)
» No flame propagation
» Flame retardant and self-extinguishing
» NF C 32-070 C1
» Good EMC characteristics
» PFAS free

Construction

Conductor
bare copper strands acc. to IEC 60228, VDE 0295, class 5
Insulation

SABIX®

Color Code

black conductors with consecutive numbers acc. to EN 50334 + VDE 0293-334
from 3 conductors: green/yellow ground

Stranding

in layers

Wrappingfoil
Shieldingtinned copper braiding
Jacket MaterialSABIX®
Jacket colorblack (RAL 9005)
Shaperound

Technical Specifications

Nominal voltage

Uo/U 450/750 V

Testing voltage

conductor/conductor: 2500 V
conductor/shielding: 2500 V

Minimum bending radius

fixed installation: 5 x O.D.
free movement: 10 x O.D.

Radiation resistance

1 x 107 cJ/kg (100 kGy)

Temperature Range

DIN VDE:
static: -30/+90°C
flexible: -20/+90°C

Halogen-free
acc. to IEC 60754-1 + VDE 0482-754-1
Burning Characteristics

Flame Propagation:
no flame propagation
acc. to IEC 60332-3-24 + VDE 0482-332-3-24
resp. IEC 60332-3-25 + VDE 0482-332-3-25 cat. C resp. D

Fire Performance:
flame retardant and self-extinguishing acc. to IEC 60332-1-2 + VDE 0482-332-1-2 + NF C32-070 C1

Smoke Densityacc. to IEC 61034 + VDE 0482-1034
Corrosiveness of conflagration gasesin compliance with IEC 60332-1-2 + VDE 0482-332-1-2 - no development of corrosive conflagration gases
Approvals
CE, RoHS
Absence of harmful substance (RoHS)acc. to RoHS directive of the European Union

Additional Information

Product highlight:
» acc. to NF C32-070 C1

Part Numbers

Part notes:

2 conductor cable does not have ground.
Other dimensions and colors are available on request.

U.S. Headquarters

SAB North America

344 Kaplan Drive, Fairfield, NJ 07004

SAB North America © 2025