SABIX® A 224 FRNC C1 - 20 AWG/2c - low smoke, halogen-free SABIX® control cable with black numbered conductors with improved fire performance and temperature range - 750V, +90°C, CE
Download PDF| Dimensions | 20 AWG/2c |
| mm2 | 0.5 |
| AWG | 20 |
| # of Conductors | 2 |
| Color Code | black numbered conductors |
| Jacket | Black SABIX (RAL 9005) |
| Outer Ø ±10% (in) | 0.228 |
| Outer Ø ±10% (mm) | 5.80 |
| Voltage | 750 |
| Cable Weight (≈lbs/mft) | 24 |
| Conductor | bare copper strands acc. to IEC 60228, VDE 0295, class 5 |
| Insulation | SABIX® |
| Color Code | black conductors with consecutive numbers acc. to EN 50334 + VDE 0293-334 |
| Stranding | in layers |
| Jacket Material | SABIX® |
| Jacket color | black (RAL 9005) |
| Nominal voltage | Uo/U 450/750 V |
| Testing voltage | conductor/conductor: 3000 V |
| Minimum bending radius | fixed installation: 4 x O.D. |
| Radiation resistance | 1 x 107 cJ/kg (100 kGy) |
| Temperature Range | DIN VDE: |
| Halogen-free | acc. to IEC 60754-1 + VDE 0482-754-1 |
| Burning Characteristics | Flame Propagation: |
| Smoke Density | acc. to IEC 61034 + VDE 0482-1034 |
| Corrosiveness of conflagration gases | in compliance with IEC 60332-1-2 + VDE 0482-332-1-2 no development of corrosive conflagration gases |
| For flexible application | very good |
| Application in track | not recommended |
| Approvals | CE, RoHS |
| Absence of harmful substance (RoHS) | acc. to RoHS directive of the European Union |
Part notes: