Products

Flexible Control Cables

CC 600 P

Flexible & Oil Resistant Polyurethane Control Cables with UL/CSA

SERIES #: 0261

Oil resistant, tear resistant, flexible PVC insulated and PUR jacketed control cable with black numbered conductors - 600V, +80°C

Download PDF
CC 600 P- SAB Flexible Control Cables

Marking for CC 600 P 2611604:
SAB BRÖCKSKES · D-VIERSEN · 2611604 4 x 1.5 mm² CC 600 P 16 AWG/4c 02610415 UR AWM Style 21060 80°C 600V CSA AWM I/II A/B 80°C 600V FT1 FT2 CE

RU
CSA
NFPA 79
CE
RoHS
PFAS-Free

Application

Tailored for industrial use, the CC 600 P series ensures long-lasting performance in control wiring projects. Oil-resistant, tear resistant, flexible PVC insulated and PUR jacketed control cable with black numbered conductors - rated for 600 V, up to 80°C. It is built with a PU acc. to UL 758 jacket for durability and resistance in harsh conditions. With approvals such as UR AWM, CSA AWM, CE, RoHS, it meets key international standards. This series also offers oil-resistant, chemical resistance to perform in demanding environments. The result is dependable connectivity that keeps machinery and automation running at peak performance.

Outstanding Features

» UL recognized, CSA approved
» Oil resistant
» Abrasion resistant jacket
» Notch resistant
» Good chemical resistance
» NFPA 79 for industrial machinery
» PFSA free

Construction

Conductor
bare copper strands acc. to IEC 60228, VDE 0295, class 5
Insulation
PVC, TI2 acc. to EN 50363-3 + VDE 0207-363-3
Color Code

black conductors with consecutive numbers acc. to EN 50334 + VDE 0293-334
from 3 conductors: green/yellow ground

Stranding
in layers
Inner Jacketfrom 12 AWG: PVC, TM2 acc. to EN 50363-3 + VDE 0207-363-3
Jacket MaterialPU acc. to UL 758
Jacket colorgray (RAL 7000)

Technical Specifications

Nominal voltage
Uo/U 300/500 V
Voltage

UR/CSA: 600 V

Testing voltage

conductor/conductor: 2000 V

Minimum bending radius

fixed installation: 4 x O.D.
free movement: 6 x O.D.

Radiation resistance
5 x 107 cJ/kg
Temperature Range

UR/CSA: up to +80°C

DIN VDE: 
static: -40/+70°C
flexible: +5/+70°C

Burning Characteristics

Fire Performance:
flame retardant and self-extinguishing
acc. to IEC 60332-1-2 + VDE 0482-332-1-2
UL VW-1, CSA FT1, FT2

Oil resistance
very good - oil rating 60°C acc. to UL 1581
Chemical resistance
good - against acids, akalines, solvents, hydraulic liquids, etc.
For flexible applicationsuitable
Application in cable tracknot recommended
Machinery areayes
Approvals
UR AWM, CSA AWM, CE, RoHS
Absence of harmful substance (RoHS)acc. to RoHS directive of the European Union

Additional Information

Possible on request:

» blue or red conductors

» black or orange jacket

Part Numbers

Part notes:

2 conductor cable does not have ground.
Other dimensions and colors are available on request.

U.S. Headquarters

SAB North America

344 Kaplan Drive, Fairfield, NJ 07004

SAB North America © 2025