Products

ETFE, FEP, & PFA Cables

TD 833 CF

Connection and data cables with extended temperature range

SERIES #: 3833

Shielded chemical and solvent resistant FEP data cable with colored conductors and overall copper shield with extended temperature range - 600V, +180°C

Download PDF
TD 833 CF- SAB ETFE, FEP and FPA Cables

Marking for TD 833 CF 38330320:
SAB BRÖCKSKES · D-VIERSEN · TD 833 CF AWG 20/3c cURus AWM Style 21618 I/II A/B 150°C 600V FT1 FT2 3833-0320 CE

RU
cURus
CE
RoHS

Application

Engineered for durability, the TD 833 CF series is designed to perform in demanding environments. This shielded FEP data cable features colored conductors with an overall copper braid, providing excellent protection against electrical interference. Rated for 600 V and suitable for continuous operation up to +180°C, its FEP 6YM1 jacket (acc. to VDE 0207-6) ensures long service life under harsh thermal, chemical, and mechanical conditions. Certified to UR, cURus, CE, and RoHS, the TD 833 CF series combines oil resistance, chemical resistance, and solvent durability with reliable electrical performance. Its shielding enhances EMC characteristics, ensuring precise, high-speed data transmission in high-frequency, broadband, coaxial, and microwave applications. Recommended for chemical industry, furnace construction, brick works, heating appliances, and other high-temperature installations, the TD 833 CF series delivers stable signal integrity, robust resistance, and reliable integration into advanced control systems.

Outstanding Features

» Excellent resistance against chemicals and solvents
» Excellent temperature resistance and flexibility at low temperatures
» Excellent electrical insulating characteristics with low, nearly frequency-independent dielectric characteristics
» UL / cUL recognized

Construction

Conductor
tinned copper strands acc. to ASTM B 286
Insulation
FEP, 6Y11 acc. to VDE 0207-6
Color Code

DIN 47100: see part number

Stranding
in layers
WrappingPETP foil
Shieldingtinned copper braiding
Jacket MaterialFEP, 6YM1 acc. to VDE 0207-6
Jacket colorwhite (RAL 1013)

Technical Specifications

Peak operating voltage
max. 375 V
Voltage

UR/cUR: 600 V

Testing voltage

conductor/conductor: 2000 V
conductor/shielding: 2000 V

Minimum bending radius
7.5 x O.D.
Radiation resistance
1 x 107 cJ/kg
Temperature Range

UR/cUR: up to +150°C

DIN VDE:
static: -90/+180°C
flexible: -55/+180°C
short-term use: +200°C

Burning Characteristics

Fire Performance:
flame retardant and self-extinguishing
acc. to IEC 60332-1-2 + VDE 0482-332-1-2
UL FT1, FT2

Oil resistance
very good - acc. to UL standard 758, at 80°C after 80 days
Chemical resistance
very good - against acids, halogens, bases, chlorinated solvents as well as organic and inorganic compounds
Application in cable tracknot recommended
Approvals
UR, cURus, CE, RoHS
Absence of harmful substance (RoHS)acc. to RoHS directive of the European Union

Additional Information

Possible on request:

» ETFE or PFA insulated strands

Part Numbers

Part notes:

Other dimensions and colors are available on request.

U.S. Headquarters

SAB North America

344 Kaplan Drive, Fairfield, NJ 07004

SAB North America © 2025