Communication Cables CE

SERIES #: 0341

Shielded multi-pair PVC signal and control cable with colored conductors and overall tinned copper braid - 300V, +70°C

Download PDF
LiYDY-CY TP- SAB Data and Sensor Cables

Marking for LiYDY-CY TP 3410625:
SAB BRÖCKSKES · D-VIERSEN · LIYDY-CY TP 6 x 2 x 0.25 mm² CE

CE
RoHS
PFAS-Free

Application

With proven quality, the LiYDY-CY TP series provides consistent performance in industrial control systems. Spiral shielded multi-pair PVC signal and control cable with colored conductors and overall tinned copper braid - rated for 300 V, up to 70°C. It is built with a PVC, TM2 acc. to EN 50363-4-1 + VDE 0207-363-4-1 jacket for durability and resistance in harsh conditions. This series also offers oil- and chemical- resistance to perform in demanding environments. Its design streamlines installation and contributes to safe, efficient operations across industries. LiYDY-CY TP is a signal and control cable recommended for use in European designed computer data transmission and office equipment process control and instrumentation where maximum EMI protection is required. Twisting the conductors in paired assemblies provides interference suppression in analog or digital signals. The additional braiding on the individual pairs prevents interference between transmission circuits.

Outstanding Features

» Very good EMC characteristics
» Flexible
» PFAS free

Construction

Conductor
bare copper strands acc. to VDE 0812
Insulation
PVC, TI2 acc. to EN 50363-3 + VDE 0207-363-3
Color Code

DIN 47100: see part number

Stranding
2 conductors twisted to pairs
Shielding
wrapped pair-wise with tinned copper wires
Inner Jacketpair-wise: PVC, TM2 acc. to EN50363-4-1 + VDE 0207-363-4-1
Strandingpairs in concentric layers
WrappingPETP foil
Shieldingtinned copper braiding with a tinned copper drain wire (equal to conductor section)
Jacket MaterialPVC, TM2 acc. to EN 50363-4-1 + VDE 0207-363-4-1
Jacket colorgrayish tan (RAL 7032)

Technical Specifications

Peak operating voltage

26 AWG: max. 350 V
24 - 20 AWG: max. 500 V

Current carrying capacity
Testing voltage

conductor/conductor: 1500 V
conductor/shielding: 1200 V

Minimum bending radius

fixed installation: 5 x O.D.
free movement: 10 x O.D.

Radiation resistance
8 x 107cJ/kg
Temperature Range

DIN VDE: 
static: -30/+70°C
flexible: -5/+70°C

Burning Characteristics

Fire Performance:
flame retardant and self-extinguishing acc. to IEC 60332-1-2 + VDE 0482-332-1-2

Oil resistance
Chemical resistance
For flexible applicationsuitable
Application in cable tracknot recommended
Approvals
CE, RoHS
Absence of harmful substance (RoHS)acc. to RoHS directive of the European Union