Products

Compensation and Extension Cables

A 20-022 L

Shielded PVC Insulated Compensating and Extension Cables

SERIES #: 0426

Shielded round PVC compensation or extension cable with 2 stranded conductors together - 0.22 mm², +70°C

Download PDF
A 20 L- SAB Compensation and Extension Cables
RoHS
PFAS-Free

Application

The A 20-022 L series stands out with its adaptability and rugged design, ideal for challenging conditions. This shielded round PVC compensation or extension cable features 2 stranded conductors (0.22 mm²) and is rated for use up to 70°C. It is built with a PVC jacket, TM2 acc. to EN 50363-4-1 + VDE 0207-363-4-1, providing strength and reliability in demanding environments. The A 20-022 L is a NiCr-Ni (type K) cable with aluminum foil shielding and PETP foil wrapping. It can be used as a thermoelectric cable or as a compensating cable. NiCr-Ni cables support a temperature measuring range of -25°C to +200°C, with additional thermocouple types available upon request.

Outstanding Features

» Flame retardant and self-extinguishing
» with alu. foil shield
» PFAS free

Construction

Insulation
PVC, TI2 acc. to EN 50363-3 + VDE 0207-363-3
Stranding
2 conductors together
Shielding
alu. foil
WrappingPETP foil bare copper ground wire 0.5mm
Jacket MaterialPVC, TM2 acc. to EN 50363-4-1 + VDE 0207-363-4-1
Shaperound
Conductor constructionstrand

Technical Specifications

Minimum bending radius
7.5 x O.D.
Radiation resistance
8 x 107 cJ/kg
Insulation resistance> 1M Ω x km
Temperature Range
Temperature Range of Insulation:
DIN VDE: static: -40/+70°C
DIN VDE: flexible: +5/+70°C
Burning Characteristics
Fire Performance:
flame retardant and self-extinguishing acc. to IEC 60332-1-2 + VDE 0482-332-1-2
Approvals
RoHS
Absence of harmful substance (RoHS)acc. to RoHS directive of the European Union

Additional Information

Possible on request:

» 4, 8, or 16 pairs

Part Numbers

Part notes:

C = compensating cables · X = extension cables
DIN 43710 / 43714 (not valid for type B*): We continue to manufacture compensating and extension cables with color code acc. to DIN 43714 and the basic values of DIN 43710.
* Not standardized compensating cable for thermocouples type B with application temperatures up to 100°C resp. 200°C.