Halogen-free and flame retardant shielded SABIX® installation remote bus cable, paired + 18/3c power, 300V, 85°C
Download PDFMarking for SABIX® IBS 610 FRNC Hybrid 66106221:
SAB BRÖCKSKES · D-VIERSEN · SABIX® IBS 610 FRNC 3 x 2 x 0.22 mm² + 3 x 1.00 mm²CE
With proven quality, the SABIX® IBS 610 FRNC Hybrid series provides consistent performance in industrial control systems. This halogen-free, flame-retardant SABIX® installation remote bus cable features paired twisted conductors plus 18/3 power, rated for 300 V and up to 85°C. Its durable SABIX® jacket ensures reliability and resistance in harsh operating environments. Its halogen-free, flame-retardant design enhances safety, while UV resistance supports dependable use in demanding applications. Stranded in pairs and free of hazardous substances in compliance with EU RoHS directives, this Interbus-S cable is engineered for efficient communication and power supply in automation systems. Typical applications include manufacturing, transport, and storage technology, where safety and long service life are essential.
| Conductor | 24 AWG/3pr: bare copper strands acc. to VDE 0812 | 
| Insulation | SABIX® | 
| Color Code | 24 AWG/3pr: DIN 47100: see part number | 
| Stranding | twisted to pairs (≤ 0.25 mm²) pairs and conductors together | 
| Wrapping | PETP foil | 
| Shielding | tinned copper braiding | 
| Jacket Material | SABIX® | 
| Jacket color | red lilac (RAL 4001) | 
| Peak operating voltage | max. 350 V | 
| Testing voltage | conductor/conductor: 1500 V | 
| Minimum bending radius | 7.5 x O.D. | 
| Temperature Range | DIN VDE:  | 
| Burning Characteristics | Flame Propagation: | 
| Smoke Density | acc. to IEC 61034 + VDE 0482-1034 | 
| Corrosiveness of conflagration gases | in compliance with IEC 60754-2 + VDE 0482-754-2 - no development of corrosive conflagration gases | 
| Characteristic impedance | at 0.064 MHz: 120Ω ± 20Ω; at > 1 MHz: 100Ω ± 15Ω | 
| Weather resistance | good | 
| Direct burial | not suitable | 
| For flexible application | very good | 
| Application in track | not recommended | 
| Approvals | CE, RoHS | 
| Absence of harmful substance (RoHS) | acc. to RoHS directive of the European Union | 
Applications include:
» Interbus-S remote bus cables 3 x 2 x 0.22 mm2 or 3 x 2 x 0.25 mm2 are used for the sensor/actuator level of industrial communication
Part notes: