Products

Bus Cables

SABIX® IBS 610 FRNC Hybrid

Interbus Cables

SERIES #: 6610

Halogen-free and flame retardant shielded SABIX® installation remote bus cable, paired + 18/3c power, 300V, 85°C

Download PDF
SABIX® IBS 610 FRNC Hybrid- SAB Bus Cables

Marking for SABIX® IBS 610 FRNC Hybrid 66106221:
SAB BRÖCKSKES · D-VIERSEN · SABIX® IBS 610 FRNC 3 x 2 x 0.22 mm² + 3 x 1.00 mm²CE

CE
RoHS
PFAS-Free

Application

With proven quality, the SABIX® IBS 610 FRNC Hybrid series provides consistent performance in industrial control systems. This halogen-free, flame-retardant SABIX® installation remote bus cable features paired twisted conductors plus 18/3 power, rated for 300 V and up to 85°C. Its durable SABIX® jacket ensures reliability and resistance in harsh operating environments. Its halogen-free, flame-retardant design enhances safety, while UV resistance supports dependable use in demanding applications. Stranded in pairs and free of hazardous substances in compliance with EU RoHS directives, this Interbus-S cable is engineered for efficient communication and power supply in automation systems. Typical applications include manufacturing, transport, and storage technology, where safety and long service life are essential.

Outstanding Features

» Halogen-free
» No flame propagation
» Flame retardant and self-extinguishing
» Good weather resistance
» PFAS free

Construction

Conductor

24 AWG/3pr: bare copper strands acc. to VDE 0812
18 AWG/3c: bare copper strands acc. to IEC 60228, VDE 0295, class 6

Insulation
SABIX®
Color Code

24 AWG/3pr: DIN 47100: see part number
18 AWG/3c: red, blue and green/yellow ground

Stranding

twisted to pairs (≤ 0.25 mm²) pairs and conductors together

WrappingPETP foil
Shieldingtinned copper braiding
Jacket MaterialSABIX®
Jacket colorred lilac (RAL 4001)

Technical Specifications

Peak operating voltage
max. 350 V
Testing voltage

conductor/conductor: 1500 V
conductor/shielding: 1500 V

Minimum bending radius
7.5 x O.D.
Temperature Range

DIN VDE:
static: -40/+85°C
flexible: -30/+85°C

Burning Characteristics

Flame Propagation:
no flame propagation acc. to IEC 60332-3-24 + IEC 60332-3-25 Cat. C resp. D

Fire Performance:
flame retardant and self-extinguishing acc. to IEC 60332-1-2 + VDE 0482-332-1-2

Smoke Densityacc. to IEC 61034 + VDE 0482-1034
Corrosiveness of conflagration gasesin compliance with IEC 60754-2 + VDE 0482-754-2 - no development of corrosive conflagration gases
Characteristic impedanceat 0.064 MHz: 120Ω ± 20Ω; at > 1 MHz: 100Ω ± 15Ω
Weather resistancegood
Direct burialnot suitable
For flexible applicationvery good
Application in tracknot recommended
Approvals
CE, RoHS
Absence of harmful substance (RoHS)acc. to RoHS directive of the European Union

Additional Information

Applications include:

» Interbus-S remote bus cables 3 x 2 x 0.22 mm2 or 3 x 2 x 0.25 mm2 are used for the sensor/actuator level of industrial communication

Part Numbers

Part notes:

Other dimensions and colors are available on request.

U.S. Headquarters

SAB North America

344 Kaplan Drive, Fairfield, NJ 07004

SAB North America © 2025