Products

Bus Cables

PB 640

Profibus-DP Cables

SERIES #: 0640

Flexible PVC Profibus-DP cable with colored conductors with foil and tinned copper braid shielding - 300V, +70°C

Download PDF
PB 640- SAB Bus Cables

Marking for PB 640 6402421:
SAB BRÖCKSKES · D-VIERSEN · PB 640 24 AWG/2c 06402421 CE

CE
RoHS
PFAS-Free

Application

Designed with versatility in mind, the PB 640 series supports efficient operation in machinery and control panels. This flexible PVC Profibus-DP cable with colored conductors, foil, and tinned copper braid shielding is rated for 300 V and up to 70°C. Its PVC TM2 jacket (EN 50363-4-1) ensures durability and resistance under demanding conditions. Certified to CE and RoHS standards, the PB 640 series meets key international requirements. Its oil-resistant construction enhances reliability, making it well-suited for challenging environments. Specially optimized for speed and cost efficiency, this Profibus version was developed to support communication between automation systems and decentralized peripheral devices, ensuring dependable and efficient performance in the field.

Outstanding Features

» Flame retardant and self-extinguishing
» Short assembling time by "Fast Connect" construction
» Avoidance of connection errors
» PFAS free

Construction

Conductor

24 AWG: bare copper strands

Insulation
acc. to EN 50290-2-23 + VDE 0819-103 (02YI1)
Color Code
red, green
Stranding
in layers
Inner JacketPVC (natural)
Shieldingdouble shield: alu. foil and tinned copper braiding
Jacket MaterialPVC, TM2 acc. to EN 50363-4-1
Jacket colorred lilac (RAL 4001)

Technical Specifications

Peak operating voltage
max. 350 V
Testing voltage

conductor/conductor: 1500 V
conductor/shielding: 1500 V

Minimum bending radius
12 x O.D.
Temperature Range

DIN VDE:
static: -30/+70°C
flexible: -5/+70°C

Burning Characteristics

Fire Performance:
flame retardant and self-extinguishing acc. to IEC 60332 + VDE 0482-332-1-2

Characteristic impedance(3 - 20 MHz): 150 Ω ± 10Ω
Oil resistance
For fixed installationsuitable
For flexible applicationsuitable
Application in cable tracknot recommended
Approvals
CE, RoHS
Absence of harmful substance (RoHS)acc. to RoHS directive of the European Union