Products

Bus Cables

IBS 612 Hybrid

Interbus Cables

SERIES #: 0612

Hybrid flexible PVC Interbus-S installation remote bus cable with colored power conductors and twisted pairs for indoor and outdoor installation - 300V, +70°C

Download PDF
IBS 612 Hybrid- SAB Bus Cables

Marking for IBS 612 Hybrid 6126228:
SAB BRÖCKSKES · D-VIERSEN · IBS 612 3 x 2 x 0.22 mm² + 3 x 2 x 0,22 mm² + 3 x 1.0 mm² CE

CE
RoHS
PFAS-Free

Application

The IBS 612 Hybrid series stands out with its adaptability and rugged design, making it ideal for demanding industrial conditions. This hybrid flexible PVC Interbus-S installation remote bus cable features colored power conductors and twisted pairs, rated for 300 V and up to 70°C. Its PVC TM2 jacket (EN 50363-4-1) ensures durability and resistance in harsh operating environments. Its direct-burial, UV- and oil-resistant construction provides long service life for both indoor and outdoor applications. Designed as a shielded PVC Interbus-S cable, it supports underground installation and features a minimum bending radius of 7.5 × O.D. Optimized for communication at the field level (e.g., sensors, actuators, controllers) and for data transmission to higher control levels (e.g., SPS), the IBS 612 Hybrid delivers reliable connectivity across automation systems.

Outstanding Features

» Flame retardant and self-extinguishing
» For indoor and outdoor use
» PFAS free

Construction

Conductor

24 AWG/3pr: bare copper strands acc. to VDE 0812
18 AWG/3c: bare copper strands acc. to IEC 60228, VDE 0295, class 6

Insulation
PE, 2YI1 acc. to EN 50290-2-23 + VDE 0819-103
Color Code

24 AWG pairs: DIN 47100: see part number
18 AWG/3c: red, blue and green/yellow ground

Stranding

twisted to pairs ( 24 AWG)

WrappingPETP foil
Shieldingtinned copper braiding
Jacket MaterialPVC, TM2 acc. to EN 50363-4-1
Jacket colorblack (RAL 9005)

Technical Specifications

Peak operating voltage
max. 350 V
Testing voltage

conductor/conductor: 1500 V
conductor/shielding: 1200 V

Minimum bending radius
7.5 x O.D.
Radiation resistance
8 x 107 cJ/kg
Temperature Range

DIN VDE:
static: -30/+70°C
flexible: -5/+70°C

Burning Characteristics

Fire Performance:
flame retardant and self-extinguishing acc. to IEC 60332-1-2 + VDE 0482-332-1-2

Characteristic impedanceat 0.064 MHz: 120Ω ± 20Ω; at > 1 MHz: 100Ω ± 15Ω
Oil resistance
Weather resistancemedium
Direct burialsuitable
Flexibilitygood
Application in cable tracknot recommended
Approvals
CE, RoHS
Absence of harmful substance (RoHS)acc. to RoHS directive of the European Union

Part Numbers

Part notes: