Flame Tests for Electrical Cables

UL 1581 Section 1080 (FV-2 / VW-1 Flame Test)

Description UL 1581, § 1080 - reference to standard UL 2556, § 9.4
(VW-1 Flame Test)
Length of specimen 24.02 in. (610 mm)
Burner Bunsen burner with additional air supply (Tirril gas burner) Ø 0.37 in. (9.5 mm)
Test temperature 500 W flame
Position of specimen vertical
Position of flame 20° to vertical specimen
Duration of flame 5 x 15 seconds with least 15 seconds flaming break
Conditions The paper must be no more than 25% carbonized. The specimen may continue burning for a maximum of 1 minute after each application. Any material that drops must not ignite the cotton (B) placed beneath the specimen.
UL 1581 Section 1080 (FV-2 / VW-1 Flame Test) Setup
UL 1581 Section 1080