Flame Tests for Electrical Cables
UL 1581 Section 1061 (Cable Flame Test)
| Description | UL 1581, § 1061 (Cable Flame Test) |
| Length of specimen | 24.01 in. (610 mm) |
| Burner | Bunsen burner with additional air supply (Tirril gas burner) Ø 0.37 in. (9.5 mm) |
| Test temperature | 500 W flame |
| Position of specimen | vertical |
| Position of flame | 20° to vertical specimen |
| Duration of flame | 3 x 60 seconds with 30 seconds flaming break |
| Conditions | The paper must be no more than 25% carbonized. The specimen may continue burning for a maximum of 1 minute after each application. Any material that drops must not ignite the cotton (B) placed beneath the specimen. |
| UL 1581 Section 1061 (Cable Flame Test) Setup |
![]() |
