Flame Tests for Electrical Cables

IEC 60332-3-... & EN 60332-3-...

Description IEC 60332-3-..., EN 60332-3-...
Length of specimen 137.8 in. (3500 mm)
Burner Flat burner (Ribbon gas burner of American Gas Furnace Co.)
Test temperature Given by the prescribes gas and air flow rate
Position of specimen vertical
Position of flame horizontal
Duration of flame Category A, B: 40 minutes
Category C, D: 20 minutes
Conditions The damage or carbonization must not exceed 2.5 meters below the upper fixing clamp unless otherwise specified in the relevant standards.
  EN 60332 IEC 60332
Category A – 7.0 l/m 3 - 22 3 - 22
Category B – 3.5 l/m 3 - 23 3 - 23
Category C – 1.5 l/m > 12 mm power-ø 3 - 24 3 - 24
Category D – 0.5 l/m ≤ 12 mm power-ø
Volume of non-metallic material per meter.
3 - 25 3 - 25
IEC 60332-3 / EN 60332-3 Flame Test Setup
IEC 60332 3