EMC Grounding Gland Installation Guide

SAB’s EMC grounding glands are designed to create a path to ground and remove EMI from the cable shield at the enclosure and eventually to earth ground. We offer two designs, CG EMC-2 and CG EMC-4. SAB’s EMC glands work perfectly with VFD cables. CG EMC-2 is a more cost-effective solution for permanent installation. CG EMC-4 is designed to withstand high vibration applications and multiple re-installations of the cable. The cable can be installed in either direction when using the EMC-4 style but must be installed from the dome end for the CG EMC-2 style.

EMC-2

EMC 2 Installation

EMC-4

EMC 4 Installation

Steps for Installation

Step 1

Install the EMC cable gland on the enclosure. Use our EMC locknut for optimal contact with the enclosure. If enclosure hole is threaded, refer to the Torque Value Tables for recommended tightening torques for cap, body, and locknut.

EMC Step 1
Step 2

Prepare the cable shield for connection. Determine the spot where the cable will enter the enclosure and mark the jacket. From that first mark, measure out from the direction leaving the enclosure with “b” then “a” using the sizing chart below.

Option 1: Remove the complete jacket and trim the braid beyond the connection to the gland. Use adhesive tape to secure the end of the shield to avoid fraying.

Option 2: Leave the jacket on the cable exposing only section “b”, so contact is made with the shield. If the jacket moves during installation, gently move it back into position.

EMC Step 2
Step 3

Insert cable through gland aligning mark “a” with top of gland. Make sure the gland’s grounding springs are in contact with the shield of the cable.

•  For CG-EMC-2, do not try to rotate or pull out the cable.
•  For CG-EMC-4, the cable can be moved to ensure best position.

EMC Step 3
Step 4

Tighten the cap. Refer to Torque Values Tables for proper tightening. Once the gland is secured, do not pull or rotate the cable because this could damage the cable.

EMC Step 4

EMC-2

Metric PG NPT Marking “a” Exposed Shield “b”
inch mm inch mm
EM2-12 EP2-7 - 0.591 15.0 0.492 12.5
EM2-16 EP2-9 - 0.709 18.0 0.433 11.0
EM2-16C EP2-11 EN2-3/8 0.748 19.0 0.512 13.0
EM2-20 EP2-13 EN2-1/2 0.728 18.5 0.492 12.5
EM2-25 EP2-16 - 0.807 20.5 0.531 13.5
EM2-25C, EM2-32 EP2-21 EN2-3/4 0.945 24.0 0.591 15.0
EM2-32C, EM2-40 EP2-29 EN2-1 1.142 29.0 0.650 16.5
EM2-40C, EM2-50 EM2-50 - 1.378 35.0 0.827 21.0
EM2-50C EP2-42 - 1.260 32.0 0.906 23.0
EM2-63 EP2-48 - 1.339 34.0 1.280 32.5

EMC-4

Metric PG NPT Marking “a” Exposed Shield “b”
inch mm inch mm
EM4-12 EP4-7 EN4-1/4 0.413 10.5 0.551 14.0
EM4-16 EP4-11 EN4-3/8 0.591 15.0 0.551 14.0
EM4-20 EP4-13 EN4-1/2 0.551 14.0 0.748 19.0
EM4-20C EP4-16 EN4-1/2C 0.591 15.0 0.748 19.0
EM4-25 EP4-21 EN4-3/4 0.748 19.0 0.787 20.0
EM4-32 EP4-29 EN4-1 0.827 21.0 1.024 26.0
EM4-40 EP4-36 EN4-1 1/4 1.024 26.0 1.102 28.0
EM4-50 EP4-42 EN4-1 1/2 1.024 26.0 1.575 40.0
EM4-63 EP4-48 EN4-2 1.083 27.5 1.378 35.0
EM4-63C - - 1.220 31.0 1.378 35.0