TR 600 S-HL - 8 AWG/4c

Part #: 93380804
UL
RU
cUL
CSA
NFPA 79
CE
RoHS
PFAS-Free

Outstanding Features

» Flexible stranding for easy installation
» UL Oil Res I - oil resistant
» NFPA 79 for industrial machinery
» UL 1277: UL TC-ER-HL (exposed runs + hazardous locations)
» Submersible pump (14 AWG ≥ 3 thru 7 cond.)
» UL 2277: WTTC: Wind Turbine Tray Cable
» Class 1 Div 1 per NEC Article 501.10 (A)(1) & (2)
» 90°C Wet Rated
» PFAS free

Questions?

TR 600 S-HL

Part #: 93380804

TR 600 S-HL - 8 AWG/4c - UV and oil-resistant, flexible black PVC tray cable with black numbered conductors for hazardous locations, type TC-ER, MTW, WTTC, and +90°C Wet/Dry - 600V, +105°C, UL listed, CSA approved, Class 1 Div 1

Download PDF

Cable Configuration

Dimensions8 AWG/4c
mm210
AWG8
# of Conductors with ground4
Color Code
black numbered conductors including a green/yellow ground
JacketBlack special oil resistant pressure extruded PVC (RAL 9005)
Outer Ø (in)0.728
Outer Ø (mm)18.50
Voltage600
Cable Weight (≈lbs/mft)388

Construction

Conductor

bare copper strands, class K
(30 AWG multiple strands)

Insulation

special formulated PVC/Nylon

Color Code

black conductors with consecutive numbers
from 3 conductors: green/yellow ground

Stranding

in layers

Jacket Materialspecial oil resistant pressure extruded PVC
Jacket colorblack (RAL 9005)
Shaperound

Technical Specifications

Voltage

UL/UR AWM: 600 V
CSA: 600 V
UL WTTC: 1000 V
CSA AWM: 1000 V

Testing voltage

2500 V

Minimum bending radius

fixed installation: 4 x O.D.
free movement: 6 x O.D.

Temperature Range

UL/CSA: up to +90°C
UR AWM: up to +105°C

static: -40°C

Burning Characteristics

Fire Performance:
UL/CSA FT 4

Oil resistance

UL Oil Res I

Sunlight resistanceyes
Exposed runsyes
Cold bend test-40°C
Direct burialsuitable
For flexible applicationvery good
Application in tracknot recommended
Machinery areayes
ApprovalsUL TC-ER, UL MTW, UL WTTC, UR AWM, c(UL) CIC-TC, CSA AWM, NFPA 79, CE, RoHS, PFAS-Free
Absence of harmful substance (RoHS)acc. to RoHS directive of the European Union

Part notes:

2 conductor cables are rated UL TC only.
2 conductor cable does not have ground.
UL TC-ER-JP (joist pull) available upon request.
Other dimensions and colors are available on request.

Cable Accessories