GP 400 TF DR- 3 x 70 mm² + 3 x 12 mm² + 6 x 4 x 1.0 mm²

Part #: 34003444

Outstanding Features

» Low capacity insulation
» Abrasion resistant PUR jacket
» Cold flexible
» Halogen-free
» Oil resistant
» Weather resistant
» With wear indicator
» PFAS free
Questions?

GP 400 TF DR

Part #: 34003444

GP 400 TF DR- 3 x 70 mm² + 3 x 12 mm² + 6 x 4 x 1.0 mm², 400 Hz Ground power supply cable- TripleFlex

Download PDF

Cable Configuration

Dimensions3 x 70 mm² + 3 x 12 mm² + 6 x 4 x 1.0 mm²
mm270
AWG2/0
# of Conductors with ground3
JacketOrange PUR
Outer Ø (in)1.535
Outer Ø (mm)39.00
Voltage1000
DC resistance at 20°C max Ω/km70 mm²: 0.272; 12 mm²: 1.910; 1.0 mm²: 19.5
Voltage drop70 mm²: 0.554; 12 mm²: 3.260; 1.0 mm²: 39.0
Cable Weight (≈lbs/mft)2592

Construction

Conductor

bare copper strands, fine wires acc. to IEC 60228 class 5

Insulation
SABIX®
Color Code

1.0 mm²: white numbered conductors: 1 - 24
12 mm²: 3 x blue
70 mm²: black numbered conductors: 1 - 3

Stranding

1.0 mm²: cores twisted as quad, wrapped with overlapping non-woven tape

Strandingall elements optimized stranded in layers, wrapped with overlapping non-woven tape
Inner JacketPUR, red
Supporting ScreenAramid
Jacket Materialabrasion resistant PUR
Jacket coloryellow

Technical Specifications

Max. permissible operating voltageUo/U 0.6/1 kV
Nominal voltage

Uo/U 115/200 V

Testing voltage

conductor/conductor: 4000 V AC 50 Hz

Minimum bending radius

fixed installation: 4 x O.D; 
free movement: 7.5 x O.D; 
guided on pulleys: 10 x O.D
drum: min. 600 mm inner diameter

Tensile strength4050 N (15 N/mm²)
Temperature Range

DIN VDE:
static: -40/+90°C
flexible: -30/+90°C

Halogen-free

acc. to IEC 60754-1

Burning Characteristics

Fire performance:
jacket material: UL 94 V2

Oil resistance

very good - TMPU acc. to EN 50363-10-2

Oil and fuel resistancepetrol, diesel, and kerosene (Jet A-1)
MUD resistancevery good - acc. to IEC 60092-360
Weather resistancevery good - acc. to HD 605 (VDE 0276-605)
Ozone resistancevery good - acc. to EN 50396
Salt water resistancevery good - acc. to UL 1309
Mechanical characteristics

the main mechanical characteristics accomplished by the outer jacket are:
» very high tensile strength
» very high tear strength
» very high abrasion resistance
» very high notch resistance
» very high shear strength

Absence of harmful substance (RoHS)acc. to RoHS directive of the European Union

Part notes:

Other dimensions and colors are available on request.