GP 400 Sy - PUR - 7 x 35 mm² + 6 x 4 x 1.0 mm²

Part #: 34000452
CE
RoHS
PFAS-Free

Outstanding Features

» Price optimized
» Low capacity insulation
Questions?

GP 400 Sy - PUR

Part #: 34000452

GP 400 Sy - PUR - 7 x 35 mm² + 6 x 4 x 1.0 mm² - 400 Hz Ground Power supply cable - symmetrical for fixed installations- 1000V, +90°C, CE

Download PDF

Cable Configuration

Dimensions7 x 35 mm² + 6 x 4 x 1.0 mm²
# of Conductors30
Color Code
1.0 mm²: black numbered conductors: 1 - 24
35 mm² or 50 mm²: blue, 2 x white, 2 x brown, 2 x black
JacketOrange PUR
Outer Ø (in)min. 1.575 - max. 1.650
Outer Ø (mm)min. 40 - max. 41.9
Voltage1000
Ohmic resistance at 20°C max Ω/km35 mm²: 0.554 | 1.0 mm²: 19.5
Cable Weight (≈lbs/mft)2164

Construction

Conductor

bare copper strands, fine wires acc. to IEC 60228 class 5

Insulation
SABIX®
Color Code

34000452:
1.0 mm²: black numbered conductors: 1 - 24
35 mm²: blue, 2 x white, 2 x brown, 2 x black

34000453:
1.0 mm²: black numbered conductors: 1 - 24
50 mm²: blue, black numbered conductors

Stranding

1.0 mm²: each four conductors twisted in layers, wrapped with non-woven tape elements and 50 mm² conductors twisted in layers, blue conductor in the center, wrapped with non-woven tape

Jacket MaterialPUR
Jacket colororange

Technical Specifications

Nominal voltage

1.0 mm²:  Uo/U 115/200 V; 
50 mm²:  Uo/U max. 0.6/1 kV

Testing voltage

conductor/conductor: 4000 V AC 50 Hz

Minimum bending radius

fixed installation: 4 x O.D.
free movement: 6 x O.D.
for one single bend: 3 x O.D.

Temperature Range

DIN VDE:
static: -50/+90°C; 
flexible: -40/+90°C;
short-term use: +110°C (7500 h)

Halogen-free

acc. to IEC 60754-1

Burning Characteristics

Fire performance:
jacket material: UL 94 V2

Oil resistance

very good - acc. to EN 50363-10-2

Oil and fuel resistancepetrol, diesel, and kerosene (Jet A-1)
MUD resistancevery good - acc. to IEC 60092-360
Weather resistancevery good - acc. to HD 605 (VDE 0276-605)
Ozone resistancevery good - acc. to EN 50396
Salt water resistancevery good - acc. to UL 1309
Mechanical characteristics

the main mechanical characteristics accomplished by the outer jacket are:
» high tensile strength
» high tear strength
» high abrasion resistance
» high notch resistance
» high shear strength

ApprovalsCE, RoHS, PFAS-Free
Absence of harmful substance (RoHS)acc. to RoHS directive of the European Union

Part notes:

Other dimensions and colors are available on request.

Cable Accessories

Cable OD not specified. Use the link below to search cord grips by size.

U.S. Headquarters

SAB North America

344 Kaplan Drive, Fairfield, NJ 07004

SAB North America © 2026