SABIX® A 146 FRNC - 18 AWG/1c - green - low smoke, halogen-free wiring cable with bare copper stranding with improved fire performance and extended temperature range - 500V, +90°C, CE
Download PDF| Dimensions | 18 AWG/1c |
| mm2 | 1 |
| AWG | 18 |
| # of Conductors | 1 |
| Jacket | Green SABIX FRNC |
| Outer Ø ±10% (in) | 0.098 |
| Outer Ø ±10% (mm) | 2.50 |
| Voltage | 500 |
| Cable Weight (≈lbs/mft) | 9 |
| Conductor | bare copper strands acc. to IEC 60228, VDE 0295, class 5 |
| Jacket Material | SABIX® |
| Jacket color | 01 = black, 02 = blue, 03 = brown, 04 = gray, 05 = yellow, 06 = green, 07 = violet, 08 = white, 16 = gentian blue, 27 = green/yellow |
| Nominal voltage | Uo/U 300/500 V |
| Testing voltage | 2000 V |
| Minimum bending radius | 7.5 x O.D. 5 x O.D. (for one single bend) |
| Temperature Range | DIN VDE: |
| Halogen-free | acc. to IEC 607454-1 + VDE 0482-754-1 acc. EN 50306-1 + EN 50264-1 are fulfilled Development of HCl is < 0.5% acc. to IEC 60754-1 pH-value is > 4.3 acc. to IEC 60754-2 Conductivity is < 10.0 μS/mm acc. to IEC 60754-2 Fluoric content < 0.1% acc. to IEC 60684-2 |
| Burning Characteristics | Flame Propagation: |
| Corrosivity | in compliance with IEC 60754-2 + VDE 0482-754-2 - no development of corrosive conflagration gases |
| Smoke Density | acc. to IEC 61034 + VDE 0482-1034 |
| For flexible application | good |
| Application in track | not recommended |
| Approvals | EN 45545, UN/ECE/R118, CE, RoHS, PFAS-Free |
| Absence of harmful substance (RoHS) | acc. to RoHS directive of the European Union |
Part notes: