CC 600 MTW - 10 AWG/7c - oil-resistant, flexible PVC control and machine tool cable with black numbered conductors - 600V, +90°C, UL Listed, CSA approved
Download PDF| Dimensions | 10 AWG (≈78/28)/7c |
| mm2 | 6 |
| AWG | 10 |
| # of Conductors with ground | 7 |
| Color Code | black numbered conductors including a green/yellow ground |
| Jacket | Gray PVC (RAL 7000) |
| Outer Ø ±10% (in) | 0.669 |
| Outer Ø ±10% (mm) | 17.00 |
| Voltage | 600 |
| Cable Weight (≈lbs/mft) | 392 |
| Conductor | bare copper strands acc. to IEC 60228, VDE 0295, class 5 UL standard 758 table 5.1 UL 1581 table 20.1 |
| Insulation | special formulated PVC/Nylon |
| Color Code | black conductors with consecutive numbers acc. to EN 50334 + VDE 0293-334 |
| Stranding | in layers |
| Jacket Material | special oil resistant PVC |
| Jacket color | gray (RAL 7000) |
| Voltage | UL: 600 V |
| Testing voltage | conductor/conductor: 4000 V |
| Minimum bending radius | fixed installation: 4 x O.D. |
| Radiation resistance | 8 x 107 cJ/kg |
| Temperature Range | UL/CSA: -25/+90°C |
| Burning Characteristics | Fire Performance: |
| Oil resistance | very good - TM5 acc. to EN 50363-4-1 + VDE 0207-363-4-1 oil 60°C acc. to UL 758 fuel oil acc. to CSA-C 22.2 No. 210 |
| For flexible application | very good |
| Application in track | not recommended |
| Impact and crush test | acc. to UL 1277 |
| Machinery area | yes |
| Approvals | UL MTW, UR AWM, CSA AWM, NFPA 79, CE, RoHS, PFAS-Free |
| Absence of harmful substance (RoHS) | acc. to RoHS directive of the European Union |
Part notes:
U.S. Headquarters
SAB North America
344 Kaplan Drive, Fairfield, NJ 07004
SAB North America © 2025