CC 600 CP - 14 AWG/18c - shielded, oil-resistant, tear-resistant, flexible PVC insulated and polyurethane (PUR) jacketed control cable with black numbered conductors - 600V, +80°C, UL recognized, CSA approved
Download PDF| Dimensions | 14 AWG (≈46/30)/18c |
| mm2 | 2.5 |
| AWG | 14 |
| # of Conductors with ground | 18 |
| Color Code | black numbered conductors including a green/yellow ground |
| Jacket | Gray PVC (RAL 7000) |
| Outer Ø ±10% (in) | 0.752 |
| Outer Ø ±10% (mm) | 19.10 |
| Voltage | 600 |
| Cable Weight (≈lbs/mft) | 473 |
| Conductor | bare copper strands acc. to IEC 60228, VDE 0295, class 5 |
| Insulation | PVC, TI2 acc. to EN 50363-3 + VDE 0207-363-3 |
| Color Code | black conductors with consecutive numbers acc. to EN 50334 + VDE 0293-334 |
| Stranding | in layers |
| Wrapping | PETP foil |
| Shielding | tinned copper braiding |
| Wrapping | non-woven tape |
| Jacket Material | PU acc. to UL 758 |
| Jacket color | gray (RAL 7000) |
| Nominal voltage | Uo/U 300/500 V |
| Voltage | UR/CSA: 600 V |
| Testing voltage | conductor/conductor: 2000 V |
| Minimum bending radius | fixed installation: 5 x O.D. |
| Radiation resistance | 5 x 107 cJ/kg |
| Temperature Range | UR/CSA: up to +80°C |
| Burning Characteristics | Fire Performance: |
| Oil resistance | very good - oil rating 60°C acc. to UL 1581 |
| Chemical resistance | good - against acids, akalines, solvents, hydraulic liquids, etc. |
| For flexible application | very good |
| Application in track | not recommended |
| Machinery area | yes |
| Approvals | UR AWM, CSA AWM, NFPA 79, CE, RoHS, PFAS-Free |
| Absence of harmful substance (RoHS) | acc. to RoHS directive of the European Union |