LiYCY - 26 AWG/18c - shielded, multi-conductor, PVC signal and control cable with colored conductors and overall tinned copper braid - 300V, +70°C, CE
Download PDF| Dimensions | 26 AWG (≈18/38)/18c |
| mm2 | 0.14 |
| AWG | 26 |
| # of Conductors | 18 |
| Color Code | #1- white, #2- brown, #3- green, #4- yellow, #5- gray, #6- pink, #7- blue, #8- red, #9- black, #10- violet, #11- gray-pink, #12- red-blue, #13- white-green, #14- brown-green, #15- white-yellow, #16- yellow-brown, #17- white-gray, #18- gray-brown |
| Jacket | Grayish Tan PVC (RAL 7032) |
| Outer Ø ±10% (in) | 0.276 |
| Outer Ø ±10% (mm) | 7.00 |
| Voltage | 300 |
| Cable Weight (≈lbs/mft) | 50 |
| Conductor | bare copper strands acc. to VDE 0812 |
| Insulation | PVC, TI2 acc. to EN 50363-3 + VDE 0207-363-3 |
| Color Code | DIN 47100: see part number |
| Stranding | in layers |
| Wrapping | PETP foil |
| Shielding | tinned copper braiding |
| Jacket Material | PVC, TM2 acc. to EN 50363-4-1 + VDE 0207-363-4-1 |
| Jacket color | grayish tan (RAL 7032) |
| Peak operating voltage | 26 AWG: max. 350 V |
| Current carrying capacity | |
| Testing voltage | conductor/conductor: 1500 V |
| Minimum bending radius | fixed installation: 5 x O.D. |
| Radiation resistance | 8 x 107 cJ/kg |
| Temperature Range | DIN VDE: |
| Burning Characteristics | Fire Performance: |
| Oil resistance | |
| Chemical resistance | |
| For flexible application | good |
| Application in track | not recommended |
| Approvals | CE, RoHS |
| Absence of harmful substance (RoHS) | acc. to RoHS directive of the European Union |
Part notes: