A 6 D - 16 AWG/2c

Part #: 4288922
RoHS
PFAS-Free

Outstanding Features

» Flame retardant and self-extinguishing
» with alu. foil shield
» PFAS free
Questions?

A 6 D

Part #: 4288922

A 6 D - 16 AWG/2c - round 1.5 mm² Besilen® compensating cable with 2 solid silicone insulated conductors together and alu. foil shielding for Type B thermocouples - +180°C

Download PDF

Cable Configuration

Dimensions16 AWG/2c
mm21.5
AWG16
# of Conductors2
JacketBesilen (silicone)
For thermocouple typeType B
EMK at 100°C in mv0.033
Cable typeBC-200
Descriptioncompensating cable
Outer Ø (in)0.252
Outer Ø (mm)6.40
Cable Weight (≈lbs/mft)4

Construction

Insulation
Besilen® EI2 acc. to EN 50363-1 + VDE 0207-363-1
Stranding
2 conductors together
WrappingPETP foil, bare copper ground wire 0.5 mm
Shieldingalu foil
Jacket MaterialBesilen® EM9 acc. to EN 50363-2-1 + VDE 0207-363-2-1
Shaperound
Conductor constructionwire

Technical Specifications

Minimum bending radius
12 x O.D.
Radiation resistance
2 x 107 cJ/kg
Insulation resistance> 1M Ω x km
Temperature Range

DIN VDE:
static: -40/+180°C
flexible: -25/+180°C
short-term use: +250°C

Halogen-free
acc. to IEC 60754-1 + VDE 0482-754-1
Burning Characteristics

Fire Performance:
flame retardant and self-extinguishing acc. to IEC 60332-1-2 + VDE 0482-332-1-2

Corrosivityin compliance with IEC 60754-2 + VDE 0482-754-2 - no development of corrosive conflagration gases
For flexible applicationgood
Application in tracknot recommended
ApprovalsRoHS, PFAS-Free
Absence of harmful substance (RoHS)acc. to RoHS directive of the European Union

Part notes:

C = compensating cables · X = extension cables
DIN 43710 / 43714 (not valid for type B*): We continue to manufacture compensating and extension cables with color code acc. to DIN 43714 and the basic values of DIN 43710.
* Not standardized compensating cable for thermocouples type B with application temperatures up to 100°C resp. 200°C.

U.S. Headquarters

SAB North America

344 Kaplan Drive, Fairfield, NJ 07004

SAB North America © 2025